The short answer: Phone carriers are shutting down the copper landlines (POTS lines) that many fire alarm panels and elevator phones still use to call for help. In March 2026, the FCC streamlined the rules for retiring that copper, which shortens the warning you will get. If your building’s fire alarm reports over a phone line, replace that path with a listed cellular or IP communicator now, on your schedule, before a carrier notice or a dead line makes the decision for you.
POTS stands for “plain old telephone service,” the analog copper landline. For decades, commercial fire alarm panels used a digital alarm communicator transmitter (DACT) that seized a phone line and dialed the central monitoring station whenever an alarm, trouble or supervisory signal came in.
It worked because copper lines were everywhere and carried their own power. That is no longer a safe assumption.
On March 26, 2026, the FCC adopted an order that removed much of the federal approval process carriers previously needed to retire copper POTS service. Carriers now have broad authority to “grandfather” copper voice service, meaning they can stop selling it to new customers and move existing customers onto a retirement track.
Carriers were already moving. AT&T began permanently decommissioning copper infrastructure in roughly 500 wire centers starting in June 2026, about 10% of its network, and Verizon, Lumen, Frontier and others have filed their own retirement notices, with most targeting full retirement between 2026 and 2029.
What this means locally: you should not count on a long runway. Even before a line is formally retired, owners report rising costs and slower repairs on legacy copper.
If the communication path fails, detectors may still sound the alarm inside the building, but nobody at the monitoring center is told. The fire department is not dispatched automatically. Your system is also out of compliance, which shows up on your next inspection and can create problems with your insurer.
Florida enforces NFPA 72, the National Fire Alarm and Signaling Code, through the Florida Fire Prevention Code. Two points matter here:
Florida’s 9th Edition Fire Prevention Code takes effect on December 31, 2026, adopting the 2022 edition of NFPA 72. If you are touching your fire alarm communications anyway, design to the current requirements.
Cellular communicator (most common). A listed module connects to the panel and sends signals over the cellular network. Many are dual-path, using two carriers or cellular plus IP.
IP communicator. Sends signals over the building’s internet connection. Typically paired with cellular as the second path, since internet service can go down in a storm.
Managed “POTS in a box” services. These emulate a copper line over cellular. They can work for some devices but must be listed and approved for fire alarm signaling. Do not assume a generic VoIP adapter is acceptable.
In many buildings, the existing fire alarm panel stays in place and only the communicator is replaced. Older panels that cannot support a modern communicator may need an upgrade. Our fire alarm upgrades guide covers when that makes financial sense.
Elevator emergency phones often run on the same copper lines as the fire alarm. ASME A17.1 requires that an elevator emergency call reach a live, authorized person, so a dead line is a code and safety issue. Read our guides on whether an elevator needs a dedicated phone line and elevator monitoring.
Are POTS lines being discontinued in Florida?
Carriers are retiring copper service in phases nationwide, and the FCC’s March 2026 order made it easier and faster for them to do so. Exact timing depends on your carrier and wire center, so check for notices and plan ahead.
Do I still need a phone line for my commercial fire alarm?
Not necessarily. NFPA 72 allows listed cellular and IP communication paths. If you keep one phone line, the second path must be a different technology.
Will I have to replace my whole fire alarm panel?
Often no. Many panels accept a new communicator. A contractor can tell you after a quick inspection.
What is a fire alarm communicator?
It is the device that sends alarm, trouble and supervisory signals from your fire alarm panel to the monitoring center. Older ones dial over a phone line; newer ones use cellular or internet.
How long does a communicator replacement take?
Usually a single service visit for a standard panel, including testing with the monitoring center.
Group One designs, installs and monitors fire alarm systems across the Treasure Coast with 24/7 UL-listed monitoring and licensed local technicians. We will inventory your lines, tell you what the panel supports and quote the replacement. Request a communicator assessment or call 772.283.2320.
Sources
– VCom Solutions, The Copper Sunset Is Real: What the FCC’s 2026 Order Means for Your POTS Lines: https://www.vcomsolutions.com/blog/copper-sunset-fcc-2026-order-pots-lines
– Fusion Connect, FCC Unanimously Clears a Faster Path to Retire Copper Networks: https://www.fusionconnect.com/blog/fcc-unanimously-clears-a-faster-path-to-retire-copper-networks-what-it-means-and-what-to-do-next
– National Training Center, fire alarm communication methods (NFPA 72-2013 DACT change): https://nationaltrainingcenter.com/?p=40163
– Minnesota State Fire Marshal, Fire Alarm Transmission Signals: https://dps.mn.gov/divisions/sfm/fire-code/fire-code-information-topic/fire-alarm-transmission-signals
– Florida Division of State Fire Marshal, Notice of Proposed Rule 69A-3.012 (NFPA 72, 2022 edition in 9th Edition FFPC): https://myfloridacfo.com/docs-sf/general-counsel-libraries/generalcounsel-documents/69a-3-012-notice-of-proposed-rule.pdf
– ICC NTA, Florida Adopts New Building Codes (effective December 31, 2026): https://www.icc-nta.org/code-update/florida-adopts-new-building-codes/
Talk to a local, licensed team, not a call center. Get a free assessment and a written quote.